Disconnect the connector for the fan motor wires according to the procedures (1) and (2) in page 2-39.
(3) Remove the lower M4 screws (Q’ty: A) fixing the suction flange.
Q’ty of Screws (A): 2 (For RPI-0.8 to 1.5FSG1)
3 (For RPI-2.0 to 4.0FSG1)
4 (For RPI-5.0FSG1)
Phillips ScrewdriverTool
(4) Remove the lower M4 screws (Q’ty: B) fixing the lower cover at the indoor fan side and remove the
lower cover.
Q’ty of Screws (B): 11 (For RPI-0.8 to 1.5FSG1)
12 (For RPI-2.0 to 5.0FSG1)
Phillips ScrewdriverTool
TURN OFF all power source switches.
Screws (M4x )
A
Suction Flange
Screws (M4x )
B