2-118
SERVICING
(2.11  Cleaning Indoor Unit Heat Exchanger)
Step
5 Protection from * Vinyl Sheet
 Cleaning Water * Adhesive Tape
* Cutter
 Cover the discharge side of the heat exchanger
 with a vinyl sheet to protect the insulation
 materials inside the unit from cleaning
 water.  Seal the vinyl sheet properly so as 
 to make no gaps with the adhesive tape.
 
NOTE:
 Perform the work by wearing gloves to
 prevent any injuries from touching the  fins
 of the heat exchanger.
 Attach the vinyl sheet to protect the
 insulation materials from the cleaning water.
 (A transparent board is also applicable
 instead of the vinyl sheet.)
6 Attaching Cleaning
 Water Pan
 Hang a cleaning water collector from the
 indoor unit.
(1) Attach ropes to the suspension brackets.
(2) Put the metal bars through the holes of
the cleaning water collector.
(3) Attach the ropes to the four bars of the
cleaning water collector and suspend
the cleaning water collector.
(4) Attach the hose to the boss of the
cleaning water collector and set
the bucket at the end of the hose.
7 Spraying the Cleaning Water  Spray the cleaning water over the fins of * Cleaning Agent
 the heat exchanger.
Procedure Required Tool
Vinyl Sheet
Heat Exchanger
Discharge Sheet Suction Sheet
Cleaning Water
Collector
Boss
Hose
Indoor Unit
Suspension
Bracket
Rope
Metal Bar
Bucket