6 Optional functions
RAS-(4-6)H(V)(R/N)(C/P)2E
SMGB0136 rev.0 - 07/2021
133
6
No. Setting Item
7-Segment
Display
Contents
19 Hot gas bypass control disabled
Initial setting
Hot gas bypass control disabled
20
Thermo-OFF setting for outdoor unit
after defrosting operation
Initial setting
Forced stop upon return from defrosting
21
Intermitent operation of outdoor fan
motor
Initial setting
Intermittent fan operation (30[s] run / 570[s] stop)
Intermittent fan operation (60[s] run / 540[s] stop)
Intermittent fan operation (120[s] run / 480[s] stop)
Intermittent fan operation (300[s] run / 300[s] stop)
22 Not prepared -
23 Not prepared -
24 Not prepared -
25 Not prepared -
26 Not prepared -
27 High static pressure mode setting
No setting
Static pressure setting
28
Crankcase heater control during
stoppage
No setting
Enable the control to restrain heater standby power
29 Not prepared -
30 Not prepared -
31 Not prepared -
32
Permit indoor fan operation during
forced stoppage
No setting
Change of forced stop state
33 Not Prepared -
34 Not Prepared -