9 Servicing
RAS-3HVRC2
SMGB0136 rev.0 - 07/2021
177
9
9.2 RAS-3HVRC2
9.2.1 Removing the pipe cover
Follow the procedure below to remove main parts and components. For mounting follow the reverse procedure of
removal.
Do not expose the refrigerant cycle to the atmosphere for a long period to avoid moisture or dust entering into the cycle.
Be sure to replace parts immediately after removing. Seal the refrigerant cycle when left unattached for a long period.
1 Remove pipe cover downward after removing 1 screw.
1
1-Pipecover
9.2.2 Removing the front cover
1 Remove the pipe cover following ”9.2.1Removingthepipecover”.
2 Remove 5 xing screws and remove the upper cover.
3 To remove the front cover remove 7 xing screws and 3 left nails.
1-Uppercover
1
2
1-Frontcover
2-Nails