2 Optional parts and installation
Optional parts and installation for RAS-3HVRC2
SMGB0136 rev.0 - 07/2021
28
2.1 Optional parts and installation for RAS-3HVRC2
Air ow guide wind guard and snow protection hood
Optional parts Model
Air ow guide AG-264
1 Air ow guide
2 Wind Guard
3 Snow protection hood
Wind guard WSP-264
Snow protection
hood
Zinc Plate
Air outlet
ASG-SP10FTB (Half)
ASG-SP11FTB (Full)
Air inlet of rear side ASG-SP10BTB
Air inlet of side face ASG-SP10LTB
Stainless plate
(NSSC180)
Air outlet
ASG-SP10FTBS (Half)
AASG-SP11FTBS (Full)
Air inlet of rear side ASG-SP10BTBS
Air inlet of side face ASG-SP10LTBS (Half)
Drain Heater DH-SP63A
2.1.1 Air ow guide AG-264
Specications
Air discharge direction Upward (downward) left and right
18
Material Weather proof polypropylene resin
Color Gray (Mussel code:1.0Y8.5/0.5)
Weight 1.7 kg
Accessories
Fixing screw 4 x [M5 (SUS) x 12] + 4 x [M5 (SUS) x 30]
Self-screw Self-screw 2x [M4 x 13]
Installation manual
Installation restriction
“Wind Guard” or “Snow protection hood” is not
available to install with air ow guide. (“Guard
net” is available to be installed together.)
Air ow guide installation
One air ow installation
• Open the holes for the attachment of the airow guide with a
M4x13 self-tapping screw at the designated locations.
• Attach the air ow guide to the air discharge grille with the
supplied M5x12 SUS screws for xing the airow guide.
• Do not remove the air discharge grille for air ow guide
installation.
! CAUTION
If the air guide is installed without discharge grille it may cause injury due to
rotating fan.
Air discharge grille
Air ow
Air ow guide
4xM5 xing screw
(Accesories)
Service space
• In case of right and left sides air discharge enough space for air
discharge is required.
• The downward air discharge is also available. In such case install
the base under the unit to secure enough space for air discharge.
• In case of serial units installation air discharge should be upward.
Min. 150 mm