9 Servicing
RAS-(4-6)H(V)(R/N)(C/P)2E
SMGB0136 rev.0 - 07/2021
199
9
15 Remove all used protections and wet cloths.
16 Move the cables until they are the same as they were originally.
17 Assembly the solenoid valve coil -1- according to the item “9.3.11Removingsolenoidvalvecoil(SVA)”.
18 Charge new refrigerant according to the item “3.4Refrigerantcharge”.
19 Assembly the electrical box according to the item “9.3.6Removingelectricalbox”.
20 Assembly the service cover according to the item “9.3.1Removingservicecover”.
9.3.15 Disassembly / Assembly the Electrical components for RAS-(4-6)HV(R/N)(C/P)2E
! DANGER
Check that all the LEDs on the inverter PCB (PCB2) are OFF. If necessary, wait a few minutes until all the LEDs are completely
switched OFF.
! CAUTION
• WhenattachingthePCB,orwhenattachingthepartsattachedtothePCB,payattentionnottoclampanywiringbetweenplatesor
electricalcomponents.
• Toconnectwiringatreassembling,ensurethattheterminalnumbersandwiringmarkbandcodesarematched.Ifconnectionsare
wrong,thereisthepossibilityofwrongoperationandtocausedamagetoelectricalparts.
Opening / Closing Electrical box (P plate)
1 Disassembly the service cover according to the item “9.3.1Removingservicecover”.
2 Remove the xing screw -1- of the electrical box upper support -2-.
3 Remove the 4 xing screws -4- of the electrical box.
4 Disassembly the more convenient cover to access inside the electrical box and cut the plastic ties -3- that xes the
lead wire to the upper support.
- Upper cover according to the item “9.3.3Removinguppercover”.
- Rear cover according to the item “9.3.4Removingbottomservicecoverandrearcover”.
2
3
1
4
4
5 Open the P plate turning it clockwise approximately 90°.
6 Close the P plate turning it counter clockwise.
7 Fix the lead wire to the upper support with two plastic ties as it was originally.
8 Assembly the cover removed on Step 4.
9 Assembly the service cover according to the item “9.3.1Removingservicecover”.