8 Electrical checks of main parts
Reactor (DCL)
SMGB0136 rev.0 - 07/2021
172
8.6 Reactor (DCL)
This part is used for changing alternating current to direct current for the inverter.
8.6.1 RAS-3HVRC2
Items Specications
Character 12 mH±15 (at 1 kHz)
Rated current 15 A
DC Resistance 160 mΩ (max.)
Permissible temperature range -25ºC to 60ºC
100
? NOTE
All measurements are in mm.
8.6.2 RAS-(4-6)HV(R/N)(C/P)2E
150
MAINTENANCE
2.9 Reader (DCL)
This part is used for changing the alternative current to the direct current for the inverter.
Model: 3HP~6.5HP
Reactor <400V/50Hz, 380-415V/50Hz, 380V/60Hz>
Items Specications
Character 0.41mH (40KHz) (DC 16A)
Rated Current 16A
Direct Current Resistance 50.0mΩ (Max) (25°C)
Model: 7HP~12HP
Items Specications
Character 1mH
Rated Voltage AC 380V/415V
Rated Current 30A
Red
Red
Black
Black
Item Specications
Condition 0.41 mH ± 10% (DC 16A)
Rated current 16 A
Direct current resistance 50.0 mΩ ± 20% (at 25°C)
? NOTE
All measurements are in mm.
8.6.3 RAS-(4-6)H(R/N)(C/P)2E
Item Specications
Condition 1.0 mH ± 10% (at 1 Khz)
Rated current 35 A
Direct current resistance 27.0 mΩ ± 20% (at 20°C)
? NOTE
All measurements are in mm.
5.4
76.8
86
75.2
66
6.553