6 Optional functions
RAS-(4-6)H(V)(R/N)(C/P)2E
SMGB0136 rev.0 - 07/2021
126
6.2.2.2 Setting of external input and output
If the initial setting has to be modied, the following instructions must be followed:
1 DSW1 PIN4 of the outdoor unit PCB must be set to “ON” before the modication in order to prevent activation of the
compressor. (The setting must be carried out during the stoppage of the outdoor unit.)
2 Set DSW2 PIN6 ON for “External Input and Output Setting”, it will be displayed on the 7-segment display.
3 Pressing PSW2 and PSW3 changes the input/output terminal name. After the each input/output name appear the
function number, pressing PSW1 it can be changed.
3
1
Input setting 2
Input setting 3
Output setting 1
Output setting 2
Input setting 1
Other items are set in the same manner
(External output can be set until function nº 4)
Function
I/O terminal
name
Function
I/O terminal
name
Function
I/O terminal
name
Function
I/O terminal
name
Function
ON
Switch setting
contents with
PSW1
4 After selecting the control function number, turn OFF DSW2 PIN6. The display will be back to the normal operation.
Then turn OFF the DSW1 PIN4. The selected data is stored in the outdoor unit PCB1 and the “External Input and
Output Setting” is completed. The stored data is maintained even when the power source is cut OFF. Refer to the
next table for the details for the electrical wiring connection and the required parts.
Specications of required main parts
Components Specications Remarks
3-pin connector cable
PCC-1A (Accesory)
(connected to a JST Connector, XARP-3)
5 cables with connectors in a single
assembly
Cable (Inside the unit) Low voltage 0.3 mm
2
Less than 24 V
? NOTE
• Theterminalcablemustbeasshortaspossible.
• Donotplacethecablesalongsidethehighvoltagecables.Maintainatleast30cmofdistancebetweenthecableandthehighvoltage
cable.Thecablesmaybecrossed.Ifnecessarytoplacethecablesalongsidethehighvoltagecable,insertthelowvoltagecables
insideametalconduitandgrounditoneoftheend.Ifsealedcablesareusedforthelowvoltagecables,grounditoneoftheendof
theshieldcable.
• Themaximumlengthmustbewithin70m.