EasyManua.ls Logo

Hitachi UTOPIA RAS-4HVRP2E - Abnormally High Operation Sound (in the Ceiling Type Indoor Unit); Alarm Code 31; Not Cooling Well Due to Insufficient Installation Space for the Outdoor Unit

Hitachi UTOPIA RAS-4HVRP2E
340 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
11 Maintenance notes
General notes
SMGB0136 rev.0 - 07/2021
325
11
11.1.4 Abnormally high operation sound (in the ceiling type indoor unit)
Question and answer for the eld work
Example 3: Abnormally high operation sound (in-the-ceiling type indoor unit)
Phenomenon The operation sound at the “HIGH” speed was abnormally high.
Cause
The indoor units were installed without the ducts. Since there was any external static pressure a big air 
volume was supplied. This resulted in a higher air speed through the heat exchanger.
Damper
Indoor unit
Air lter
Countermeasure
In order to reduce the airow set the indoor unit at “Low static pressure” setting.
11.1.5 Alarm code “31”
Question and answer for the eld work
Example 4: Alarm code “31”
Phenomenon Alarm code “31” sometimes occurred and the system stopped.
Cause
The combination of the indoor units and the outdoor unit was the following.
ON
OFFON ON ON ON
Power
Source
Power 
source
ON
ON
ON
ON
ON
OFF
This system was used in a tenant building. One of the tenant’s customers turned OFF the main switch for the 
indoor unit while other indoor units are running. This results in a different setting of the total indoor unit capacity in 
the same refrigerant cycle.
Countermeasure All the main switches for the indoor units were always ON.
11.1.6 Not cooling well due to insufcient installation space for the outdoor unit
Question and answer for the eld work
Example 5: Not cooling well due to insufcient installation space for outdoor unit
Phenomenon
Cooling operation was well performed through the intermediate season. However the cooling operation was not 
well available when the outdoor temperature was higher than 35 °C.
Cause
As the outdoor units were installed without a sufcient installation space the hot discharge air from other outdoor 
units was circulated.
In this case though the outdoor temperature was 35 °C the actual suction air temperature was nearly 50 °C and 
protection system from excessively high suction pressure was activated the frequency of the compressor was 
decreased and the cooling capacity was also decreased accordingly. 
As the outdoor units in-line were installed back to back with a certain distance between each outdoor unit’s back 
the hot discharged air from other outdoor units was circulated.
Countermeasure Ensure that sufcient space should be secured for multi-row and multiple-installation.

Table of Contents

Related product manuals