9 Servicing
RAS-(4-6)H(V)(R/N)(C/P)2E
SMGB0136 rev.0 - 07/2021
189
9
1
2
3
? NOTE
ThegurecorrespondstoaRAS-(4-6)H(R/N)(C/P)2Eunit.
11 Mount the 6 xing screws -1- of the electrical box.
12 Assembly the service cover according to the item “9.3.1Removingservicecover”.
13 Assembly the upper cover according to the item “9.3.3Removinguppercover”.
9.3.7 Removing the compressor
1 Disassembly the service cover according to the item “9.3.1Removingservicecover”.
2 Disassembly the bottom service cover and rear cover according to the item “9.3.4Removingbottomservicecover
andrearcover”.
3 Collect the refrigerant according to the item “3.4Refrigerantcharge”.
- If the outdoor unit is installed close to a wall remove the refrigerant piping and move the unit from the wall.
4 Open the soundproof cover -3- wrapped around the compressor and remove it.
5 Remove the terminal box cover -1- on top of the compressor.
? NOTE
Connectingwiresinwrongorderatreassemblingmayresultincompressordamage.