9 Servicing
RAS-(4-6)H(V)(R/N)(C/P)2E
SMGB0136 rev.0 - 07/2021
197
9
3
1
2
4
10 Remove the pipes from the reversing valve.
11 Seal the pipes with a tape to protect the reversing valve and the cycle assembly from dust.
12 Remove reversing valve -1- from the assemblies and install the new one.
13 Protect the new reversing valve -1- with a wet cloth.
14 Braze the connections -2- and -4- between the reversing valve -1- and the piping until the valve is properly installed.
15 Allow the brazing to cool down for a few minutes.
16 Remove all used protections and wet cloths.
17 Assembly the electrical box according to the item “9.3.6Removingelectricalbox”.
18 Move the cables until they are the same as they were originally.
19 Assembly the reversing valve coil -3- according to the item “9.3.9Removing4-wayvalvecoil”.
20 Charge new refrigerant according to the item “3.4Refrigerantcharge”.
21 Assembly the rear cover according to the item “9.3.4Removingbottomservicecoverandrearcover”.
22 Assembly the service cover according to the item “9.3.1Removingservicecover”.
9.3.13 Removing Electronic expansion valve
1 Disassembly the service cover according to the item “9.3.1Removingservicecover”.
2 Disassembly the rear cover according to the item“9.3.4Removingbottomservicecoverandrearcover”.
3 Disassembly the electrical box according to the item “9.3.6Removingelectricalbox”.
4 Collect the refrigerant according to the item “3.4Refrigerantcharge”.
5 Disassembly the Electronic expansion valve coil -1- according to the item “9.3.10Removingelectronicexpansion
valvecoil”.
6 Protect all the elements located around the expansion valve and the brazing area with a wet cloth.
7 Charge the stop valve for liquid with nitrogen and rell the expansion valve piping.
8 Heat the brazed connection -3- between the expansion valve -2- and the piping with a brazing unit until the brazing is
undone.
9 Remove the pipes from the expansion valve.
10 Seal the pipes with a tape to protect the reversing valve and the cycle assembly from dust.
11 Remove the electronic expansion valve -2- from the assemblies and install the new one.
12 Protect the new electronic expansion valve -2- with a wet cloth.