9 Servicing
RAS-3HVRC2
SMGB0136 rev.0 - 07/2021
180
7  Remove the suction and discharge pipes from the compressor.
Be sure to separate the blazing burner ame sufciently from the wires and electrical components around the brazed 
part in order to avoid burning.
1-BlazingDischargepipe.
2-BlazingSuctionpipe.
8  Remove push nuts 1 and 2 which xes the compressor. Lift the compressor and remove from the unit body. (3 in the 
gure does not have a push nut).
9  Check if the Faston terminal has any abnormality when replacing the compressor. (Ensure the pull out force greater 
than 20 N). If the Faston terminal is identied faulty replace to a new one.
1
2
3
Compressor
Accumulator
Push nut
Compressor
Vibration-
proof rubber
10  In case that is necessary more space to take out the compressor, remove the screw of the metal sheet.
1
1-Metalsheetscrew