3 Piping work and refrigerant charge
Refrigerant piping range
SMGB0136 rev.0 - 07/2021
57
3
ื3m
20m
30m
IU1
IU4
IU3
IU2
OU1
OU1
3m
3m
3m
3m
3m
3m
(
6m)
20m
30m
IU1
IU4
IU3
IU2
OU1
OU1
3m
3m
3m
3m
ื3m
? NOTE
All pictures are as example. Branch and headers are not showed as real sizes or real picture, for the installation of this components fol-
low the technical documentation.
Installing Distributor
1 Install the distributor supplied by Hitachi on request.
A tee can not be installed instead of a branch pipe.
2 Installing the distributor
Fix the branch pipe horizontally to the pillar, wall or ceiling. Piping must not be xed rigidly to the wall as thermal 
expansion and contraction can cause pipe fracture.