EAGLEHAWK NX CONTROLLER EVERYDAY OPERATIONS
49 EN2Z-1053GE51 R0119
7. Push the rotate&push button. The datapoint status is displayed.
8. Push the rotate&push button. The Manual checkbox is disabled.
9. Turn the rotate&push button to navigate to and highlight OK. The Station
Point List screen redisplays. The edited datapoint is removed from the list.
Setting Datapoint into Manual Mode
Purpose Sets a datapoint into manual mode and changes its value.
Procedure
1. In the HOME screen, turn the rotate&push button to navigate to and highlight
the General menu icon
.
2. Then push the rotate&push button. The General menu is displayed.
3. Turn the rotate&push button to navigate to and highlight Station Point List.
4. Push the rotate&push button.
The Station Point List screen is displayed.