EVERYDAY OPERATIONS EAGLE CONTROLLER
EN2Z-1053GE51 R0119 74
The power and status LEDs at the EAGLEHAWK controller indicate the controller´s
statuses and allows troubleshooting. Please refer to the following tables that
describe the behavior, meaning and necessary action to check status and solve
errors and/problems.
Power LED (green)
Power LED Behavior Meaning Action
1 ON Normal operation No action necessary
2 OFF Power supply not OK Check power supply voltage / wiring
Status / Alarm LED (red)
LED Behavior Meaning Service Action
1 LED remains OFF after
power-up
Normal operation
No action necessary
2 LED is lit continuously after
power-up
The controller has encountered a hardware
problem or
The application has a fault or
The controller has been powered up without an
application or
The operator has manually stopped the
application, e.g., using XW-Online. In this case,
the LED will light up 13 minutes after power-up
without application
Try powering down and then
powering up the XCL8010.
If problem persists, check and – if
necessary – reload the application.
If problem still persists, replace
hardware
Rx
Tx
RS485-1 Send (Tx) / Receive (Rx) LED (yellow)
RS485-1 LED Behavior Meaning Action
1 Both LEDs are flashing Normal operation, RS485-1 is functioning
properly
No action necessary
2 Both LEDs are OFF No RS485-1 communication
Check RS485-1 termination switch
3 Rx Led is flashing and Tx is
OFF
RS485-1 communication is switched off but
controller is receiving data from other controllers
Switch on RS485-1 communication
via the CENTRALINE NX
WORKBENCH PC tool. Hardware
may be defect if this does not work
4 Tx Led is flashing and Rx is
OFF
Controller is trying to establish a RS485-1
connection but there is no answer
RS485-1 baud rate is not correct;
other controller may have the same
device number on RS485, wiring
problem or hardware defect
, Application LEDs (yellow)
LED Behavior Meaning
1 LED is lit continuously Platform is starting
LED is flashing Platform is connected
2 LED is lit continuously Station is starting
LED is flashing Station is running