Loading Arms (3)
5 - 5 Model 1010 Application Pack CB Part No.: 4418024 - Rev. 1
Programming Manual
Minimum Blend Volume The instrument waits for minimum blend volume before triggering the
blend alarm.
Enter a value in the following range:
0 to 999 (100*)
Slow Flow Alarm If enabled, the instrument will issue an alarm if the arm flow is less than
the low percentage or greater than the high percentage.
Select one of the following options:
ENABLE
DISABLE*
Low Percentage The instrument triggers the slow flow low alarm if the arm slow flow is
less than LOW PRECENTAGE and the slow flow alarm is enabled.
Enter a value in the following range:
1 to 50.0 (1.0*)
High Percentage The instrument trigger the slow flow high alarm if the arm slow flow
exceeds HIGH PRECENTAGE and the slow flow alarm is enabled.
Enter a value in the following range:
1 to 50.0 (1.0*)
Slow Flow Alarm Delay The instrument waits until the volume reaches SLOW FLOW ALARM
DELAY before triggering the slow flow alarm.
Enter a value in the following range:
10 to 300 (10.0*)
High Flow Alarm If enabled, the instrument will trigger an alarm if the arm high flow is less
than the low percentage or greater than the high percentage.
Select one of the following options
ENABLE
DISABLE*
Low Percentage The instrument triggers the high flow low alarm if the arm high flow is
less than LOW PRECENTAGE and the high flow alarm is enabled.
Enter a value in the following range: 1 to 50.0 (1.0*)
High Percentage The instrument triggers the high flow high alarm if the arm high flow is
greater than HIGH PRECENTAGE and the high flow alarm is enabled.
Enter a value in the following range: 1 TO 50.0 (1.0*)
High Flow Alarm Delay The instrument waits until the volume reaches HIGH FLOW ALARM
DELAY before triggering high flow alarm.
Enter a value in the following range:
10 to 300 (10.0*)