Additive Lines (6)
8 - 4 Model 1010 Application Pack CB Part No.: 4418024 - Rev. 1
Programming Manual
Edit Additive n Code Allows entry of a 10-character alphanumeric description for the injection
point.
Constraints: Available only when the injector point is enabled and
assigned an arm.
Select one of the following options:
10 Character alphanumeric
Pacing volume Sets how often an additive injection will occur.
For example, enter “200” to inject additive once for every 200 L of
product, at 100 L, 300 L, 500 L and so on.
Constraints: Available only when the injector point is enabled and
assigned an arm.
Enter a value in the following range:
1 to 9999 (200*)
Pump Off Delay Sets a time period in seconds between injections during which the
pump may continue to run. This reduces the number of pump starts.
This is applicable only during the same batch, that is, for multiple
batches. The pump will shut down immediately if the transaction is
terminated.
Enter a value in the following range:
0 to 999 seconds (0*)
8.5.2 Alarm setup
Inj n Leaking Solenoid Enables or disables the Leaking Solenoid alarm for an injection point.
Constraints:
Available only when the injection point is enabled and assigned an
arm.
Select one of the following options:
Enable
Disable*
Leaking Solenoid
Time Period
Enter the time period in seconds after which the leaking solenoid alarm
should be re-ported in the case where the flow exceeds the leaking
solenoid volume limit.
Constraints:
Available only when the injection point is enabled and assigned an
arm and leaking solenoid alarm is enabled.
Enter a value in following range:
0 to 9 (5*)