4 - 16 Model 1010 Application Pack CB Part No.: 4418024 - Rev. 1
Programming Manual
Manager Reset
After the removal of the input and closure of the flow control valve,
loading is paused for the time set within the Clear/Reconnect timer.
However the operator is given the option of restarting the load once
the input is restored to an active state prior to the Clear/Reconnect
expiry. Once the timer expires the loading computer is locked out
from loading until a Manager Reset is performed by entering the
Manager Reset password (see section 4.2) into the instrument at
the password prompt or sending the MR SLIP command.
NOTE: If emergency stop input is disconnected during loading the load is
terminated. A new load cannot be started unless the Manager Reset
Password is entered into the instrument at the Password Prompt.
4.5 General Purpose Outputs (24)
Use the General Purpose Outputs sub-menu of the System menu to
assign the available General Purpose Outputs to a range of available
functions.
GP Output n Options and descriptions common to GP outputs 1 to 30.
CONFIGURE MESSAGES 27
-
1-
-
- MANAGER MESSAGES
PRESS ENTER TO SELECT
- INITIAL MESSAGES
GENERAL PURPOSE OUTPUTS 24
-
1 - DISPLAY CONTRAST
-
-
GP OUTPUT 2 - A11/A12
PRESS ENTER TO SELECT
-
GP OUTPUT 1 - A9/A10
GP OUTPUT 3 - A13/A17
-
GP OUTPUT 29 - BB16/BB17
GP OUTPUT 30 - BB18/BB17
GP Output Relay Terminal
1A1A9/A10
2A2A11/A12
3 A3 A13/A17
4 A4 A14/A17
5 A5 A15/A17
6 A6 A16/A17
7 B1 BA1/BA2
8 B2 BA2/BA3
9 B3 BA4/BA5
10 B4 BA5/BA6
11 B5 BA7/BA8
12 B6 BA9/BA8