7 - 1 Model 1010 Application Pack CB Part No.: 4418024 - Rev. 1
Programming Manual
CHAPTER 7 PRODUCT STREAMS (5)
7.1 Description
The PRODUCT STREAMS menu allows the operator to enter valve and
flow settings
7.2 Configure Streams
No Flow Timeout If there is an absence of pulses for a time exceeding this setting during
a load, the instrument will terminate the load and display an error.
Enter a value in the following range:
0 to 999 seconds (5*)
Valve Type Selects the type of flow control valve to be used on the Meter Run.
Digital*
On/Off or 2 Stage (Available only with straight loading Arm)
Constraints: For blending arm only digital valves can be used.
Deadband If the measured flow rate is within the deadband of the required flow
rate, no adjustments are made to the flow rate. This prevents
continuous adjustments to the flow valve, thereby minimising wear.
For example, for a desired flow rate of 300 and a deadband of 60, no
adjustment is made if the flow rate is between 240 and 360.
Constraints: Only for Valve Type = Digital.
Enter a value in the following range:
0 to (Slow Flow - Minimum Linear Flow Rate) (60*)
Valve Slow Flow The desired flow rate when slow flow is required at the start of a batch.
Constraints: Only for Valve Type = Digital.
Enter a value in the following range:
PRODUCT STREAMS 5
4 - STREAM 4
1 - CON
2 - STREAM 2
3 - STREAM 3
PRESS ENTER TO SELECT
1 - STREAM 1
PRODUCT STREAMS 5
4 - STREAM 4
1 - CON
2 - STREAM 2
3 - STREAM 3
PRESS ENTER TO SELECT
1 - STREAM 1