| 51
Document 800-26311_ A - April 2020
1. Select Discrete or Group and specify the available number
• Default number is Discrete (single) output 1. This is the Switched Ground Door Lock
output on the MPA1
2. Select General Settings
3. Select Scheduling
Configuration Description
Name Enter a unique name to identify the lock output
Pulse Time configure how long a device assume to be normal status such as a
hours, minutes and seconds, Maximum time is 1:45:59
Latch Toggle the start of the outputs between energized and de-energized
upon every activation (code use, interlock, or manual pulse)
Interlocks Disable/ enable interlocks. See Configuring Interlocks, page 63for
more about Interlocks
TZ Card Toggles Requires like the First Card Rule, a valid card read within the time
zone to enable the time zone (periods in which the doors are
unlocked) to take effect. Unlike the First Card Rule, however the user
can swipe the card a second time to return the doors to a locked
state.
Effective only if the output has a valid schedule for Energized in the
Section Scheduling. Both TZ Card Toggle and First Card Rule can
not be enable the same time
First Card Rule First Card Rule requires a valid card read within the time zone to
enable the time zone (period in which the doors are unlocked) to take
effect.
Note Effectively only if the output has a valid schedule for
Energized in the section Scheduling. Both TZ Card Toggle
and First Card Rule cant be enabled at the same time.
Lock Operations Specifies the output to function in Fail Secure, or Fail Safe mode in
(default) Fail Secure mode output in normal state is not active. A lock
that needs to be powered to unlock a door will use the Fail Secure
mode. If the MPA1 is not powered the output and lock remains in it
normal state.
In Fail Safe mode the output in the normal state is activated. A lock
that needs to be Powered to lock the door (e.g a magnetic lock) will
use the Fail safe mode. If the MPA 1 is not powered the output and
lock remains in its abnormal state and releases the lock.
Note The MPA1 does not have the jumpers to provide Fail Safe
operation of the lock
Configuration Description
Energized Specifies the period during which the output relay is
automatically energized (Door is unlocked), Select Schedule
(that you created in Entering a Panel Name, page 28) from the
drop down list. The Energized state of the output can be
affected by the Enabled setting for the TZ Card Toggle or First
Card Rule.
Disable Interlocks Specifies the period during which the Interlock that control
the output will be disabled, Select a Schedule (that you
created in Entering a Panel Name, page 28) from the drop-
down list.