| 97
Document 800-26311_ A - February 2020
IMPORTANT: In order to proceed to Step #3 please wait for all panels to be synchronized.
The Synchronization will remove the Common Database from the
Secondary panels. Refer to the "Synchronization Detail Chart"
Step # 3. Select the "Restore Entire Loop" option from the "System Wide Backup" once all
of the Secondary panels are registered with the Primary. Refer to the "Restore
Entire Loop Detail Chart"
Hard Default an Existing Secondary Panel (Web Mode)
Overview
This section details the synchronization process of a MPA1 "Primary | Secondary" panel
after hard defaulting an existing "Secondary" Panel in a loop of Ethernet Virtual Loop (EVL)
in Web Mode.
Primary | Secondary Panel Synchronization (Hard Default)
Step # 1. Perform a System Wide Backup
Step # 2. Perform a hard default of the Secondary panel.
Step # 3. Un-register the original Secondary panel in the Primary panel. Navigate to:
EVL Tab: Menu > Panel Configuration > Advanced > EVL Discovery.
Step # 4. Navigate to the "Advanced" Tab of the primary panel:
EVL Installations: Requires Manual Registration of the Secondary Panel.
Navigate to the EVL Discovery and "Register" the Secondary Panels.
IMPORTANT: In order to proceed to Step #5 please wait for the Secondary panel to be
synchronized. Refer to the "Synchronization Detail Chart"
Note For the Ethernet Virtual Loop (EVL) a manual registration is required.
Step # 5. Restore the System Wide Backup and select the "Restore this panel only" option.
(If a backup hadn't been performed the Panel-specific Data will need to be
re-programmed.)
Refer to the "Restore Entire Loop Detail Chart"