EasyManua.ls Logo

Honeywell MPA2C3 - FACP input set up procedure- FAIL-SAFE INSTALLATION

Honeywell MPA2C3
183 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
MPA2C3 Installation Guide 105
Note: The power source selected by the jumper settings configures the power source for the
relay. It does not configure the power source for the panel.
Caution: RJ45 door connections do not support external relay load source.
• Setting the jumpers to configure the relay contact type:
Reader mode selection jumpers
There are two sets of reader mode selection jumpers for Wiegand or OSDP mode.
In a MPA2C3 2-door panel, one set is for READER1 IN and READER1 OUT to select
Wiegand A and Wiegand B or OSDP bus 1 (OSDP1). The other set is for READER2
IN and READER2 OUT to select Wiegand A and Wiegand B or OSDP bus 2 (OSDP2).
In a MPA2C3 4-door panel, one set is for READER1 and READER3 to select Wie-
gand A and Wiegand A or OSDP bus 1 (OSDP1). The other set is for READER2 and
READER4 to select Wiegand A and Wiegand A or OSDP bus 2 (OSDP2).
Note: Both jumpers must be positioned in synchronization.Please see chapter 3.6.3
System set up for Wiegand or OSDP readers.
Note: Both jumpers must be positioned in synchronization
Note: Please see chapter 3.6.3 System set up for Wiegand or OSDP readers
Note: Both jumpers must be positioned in synchronization.Please see chapter 3.6.3
System set up for Wiegand or OSDP readers.

Table of Contents

Other manuals for Honeywell MPA2C3

Related product manuals