80 MPA2C3 Installation Guide
Door Locking Devices / Output configurations
Connect per door the locking devices for Door OUTput / Relay (OUT) to the push in
terminal blocks or the corresponding red RJ45 Door terminal.
Each Door output (or AUX output) can be configured in 2 ways, by jumpers.
1. Output selection for locking devices powered by panel’s internal power source
(12V – by default) or by external
power supply (Ext V – voltage fee contact).
Note: Current and Voltage limitations for locking power is different per power source selection.
Below tables are reflecting current and voltage limitation for 2 and 4 door system.
Table 3-10 The reflecting current and voltage limitation for 2 and 4 door system
Outputs 2-door system
Output Contact type OUT 1-2, AUX1-2 Selectable per jumper OUT 1-2, AUX1-2:
NO (Normally Open) or NC (Normally
Closed)
Relay contact max switching voltage and
current
OUT 1-2, AUX1-2 @ RJ45 500mA @ 30VDC,
(dry contact) 500mA @ 22VAC
OUT 1-2, AUX1-2 @ push in terminal block** 3A @ 30VDC,
1A @ 22VAC
Max output Voltage at Door1/AUX1 output
when OUT1, AUX1 jumper onboard "12V” is
used (wet contact)
OUT 1 @ RJ45 or 10VDC ~ 14VDC
OUT 1 @ push in terminal block**,
AUX 1 @ RJ45 or
AUX 1 @ push in terminal block**
Max output current at Door1/AUX1 output
when OUT1, AUX1 jumper onboard "12V” is
used (wet contact)
OUT 1 @ RJ45 **, 500mA per RJ45, limited to 750mA @
12VDC combined over both door output
contacts
AUX 1 @ RJ45 **
OUT 1 @ push in terminal block**, 750mA @ 12VDC combined over both door
output contacts
AUX 1 @ push in terminal block**