EasyManuals Logo

Honeywell UDC 2300 User Manual

Honeywell UDC 2300
82 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #12 background imageLoading...
Page #12 background image
Installation
4 UDC2300 Universal Digital Controller User Manual 4/00
Check
Number
Preliminary Check Description
4
Control Relay 2 and Alarm
Relay Action.
The controller has been shipped with ALARM
relays configured for N.C. (Normally Closed). If
you want to change to N.O. refer to Figure 2-1,
Jumper positions W201 and W202:
W201 is the ALARM RELAY 1 jumper.
W202 is the jumper for CONTROL RELAY #2 for
Duplex Output or 3 position step control and an
ALARM RELAY 2 for all others.
See Table 2-2 for Control Relay contact
information, and Table 2-3 for Alarm Relay
contact information.
See Alarm Relay Caution Note, Page 6.
Note: Solid State and open collector Outputs must have jumper set to
N.O. (Normally Open).
3 Position Step and Time Duplex must have Output 2-jumper (W202) set to
N.O (Normally Open).

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UDC 2300 and is the answer not in the manual?

Honeywell UDC 2300 Specifications

General IconGeneral
BrandHoneywell
ModelUDC 2300
CategoryRemote Control
LanguageEnglish

Related product manuals