Configuration
4/00 UDC2300 Universal Digital Controller User Manual 23
3.4 Tuning Set Up Group
Introduction
Tuning consists of establishing the appropriate values for the tuning constants
you are using so that your controller responds correctly to changes in process
variable and setpoint. You can start with predetermined values but you will have
to watch the system to see how to modify them. The Accutune feature
automatically selects Gain, Rate, and Reset on demand.
ATTENTION
Because this group contains functions that have to do with security and lockout, we
recommend that you configure this group last, after all other configuration data has
been loaded.
Function Prompts
Table 3-3 TUNING Group (Numeric Code 200) Function Prompts
Prompt Selection or Range of Setting
English Numeric
Code
Description
Numeric
Code
English
Factory
Setting
PB or
GAIN
201 Proportional
Band or Gain
PB = 0.1 to 1000 %
Gain = 0.01 to 1000
1.0
RATE T
202 Rate in Minutes
0.00 to 10.00 minutes
0.08 or less = OFF
0.00
I MIN
or
I RPM
203 Reset in
minutes/repeat
Reset in
repeats/minute
0.02 to 50.00
0.02 to 50.00
1.0
1.0
MANRST
204 Manual Reset -100 to 100 % Output 0.0
PB 2 or
GAIN 2
205 Proportional
Band 2 or Gain
2
PB = 0.1 to 1000 %
Gain = 0.01 to 1000
1.0
RATE2T
206 Rate 2 in
Minutes
0.00 to 10.00 minutes
0.08 or less = OFF
0.00
I2 MIN
or
I2 RPM
207 Reset in
minutes/repeat
Reset in
repeats/minute
0.02 to 50.00
0.02 to 50.00
1.0
1.0
Table continued next page