Configuration
34 UDC2300 Universal Digital Controller User Manual 4/00
3.11 Options Set Up Group
Function Prompts
Table 3-10 Options Group (Numeric Code 900) Function Prompts
Prompt Selection or Range of Setting
English Numeric
Code
Description
Numeric
Code
English
Factory
Setting
AUXOUT
901 Auxiliary
Output
0
1
2
3
4
5
6
7
DIS Disabled
IN1 Input 1
IN2 Input 2
PROC Process Variable
DEV Deviation
OUT Output
SP Setpoint
LSP1 Local Setpoint 1
DIS
0 PCT
902 Auxiliary
Output Low
Scaling Factor
Value in Engineering Units 0
100 PCT
903 Auxiliary
Output High
Scaling Factor
Value in Engineering Units 100
DIG IN
904 Digital Input
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
17
None
MAN To Manual
LSP To Local SP 1
SP2 To Local SP 2
DIR Direct Control
HOLD Hold SPP/SP Ramp
PID2 PID Set 2
RUN Start a stopped
SPP/SP Ramp
Begn SPP Reset
NO I Inhibit Integral
MNFS Manual, Failsafe
Output
LOCK Keyboard Disable
TIMR Start Timer
TUNE Start Tune
INIT Init SP to PV
RSP Remote SP
MNLT Latching Manual
TRAK Output tracks Input 2
NONE
DI COM
905 Digital Input
Combinations
0
1
2
3
4
5
DIS Disabled
+ PD2 PID Set 2
+DIR Direct
+SP2 Set Point 2
+SP1 Set Point 1
+RUN Start SPP
DIS