Setpoint Rate/Ramp/Program Operation
64 UDC2300 Universal Digital Controller User Manual 4/00
500
400
200
300
°
F
Time/Hours
0 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
SEG 2
SEG 3
SEG 4
SEG 5
SEG 6
SEG 7
SEG 8
SEG 9
SG 10
SG 11
SG 12
SEG 1
F
20765
Setpoint
Figure 5-1 Ramp/Soak Profile Example
Ramp/Soak Profile Example
Prompt Function Segment Value Prompt Function Segment Value
STRSEG Start Seg. 1 SG4 TI Soak Time 4 1 hr.
ENDSEG End Seg. 12 SG5 RP Ramp Time 5 1hr.:30 min.
RP UNIT Engr. Unit
for Ramp
TIME SG6 SP Soak SP 6 250
PG END Controller
Status
LAST SP SG6 TI Soak Time 6 3hr.:0min.
STATE Controller
State at end
HOLD SG7 RP Ramp Time 7 2hr.:30min.
TO BEGIN Reset SP
Program
DIS SG8 SP Soak SP 8 500
PVSTRT Program
starts at PV
value
DIS SG8 TI Soak Time 8 0hr.:30 min.
RECYCL Number of
Recycles
2 SG9 RP Ramp Time 9 0
SOKDEV Deviation
Value
0 SG10 SP Soak SP 10 400
SG1 RP Ramp Time 1 1 hr. SG10 TI Soak Time 10 0hr.:30 min.
SG2 SP Soak SP 2 300 SG11 RP Ramp Time 11 3hr.:30min.
SG2 TI Soak Time 2 1hr.:30 min. SG12 SP Soak SP 12 200
SG3 RP Ramp Time 3 1hr. SG12TI Soak Time 12 0hr.:30 min.
SG4 SP Soak SP 4 400