Setpoint Rate/Ramp/Program Operation
4/00 UDC2300 Universal Digital Controller User Manual 59
5 Setpoint Rate/Ramp/Program Operation
5.1 Setpoint Rate
Introduction
When you have configured a SETPOINT RATE, it will apply immediately to local
setpoint change.
Configuration check
Make sure:
SPRATE is enabled
SPRAMP and SPPROG are disabled
A Rate Up (EUHRUP) or Rate Down (EUHRDN) value has been configured
in Engineering units per hour.
ATTENTION: A value of 0 will imply an immediate change in setpoint, that is,
NO RATE applies. See Subsection 3.5 Configuration group SPRAMP for
details.)
Operation
When a change to local setpoint is made, this controller will ramp from the
original setpoint to the target setpoint at the rate specified.
The current setpoint value can be viewed at Sn on the lower display.
Power outages
If power is lost before the target setpoint is reached, upon power recovery, the
controller powers up with Sn = Current PV value and it automatically Restarts
from Sn = current PV value up to the original target setpoint.
5.2 Setpoint Ramp
Introduction
When you have configured a SETPOINT RAMP, the ramp will occur between the
current local setpoint and a final local setpoint over a time interval of from 1 to
255 minutes. You can RUN or HOLD the ramp at any time.
Configuration Check
Make sure
SPRAMP is enabled