Configuration
4/00 UDC2300 Universal Digital Controller User Manual 37
3.13 Alarms Set Up Group
Function Prompts
Table 3-12 ALARMS Group (Numeric Code 1100) Function Prompts
Prompt Selection or Range of Setting
English Numeric
Code
Description
Numeric
Code
English
Factory
Setting
AxSxVA
A1S1
A1S2
A2S1
A2S2
1101
1102
1103
1104
Alarm Setpointx
Value
X = 1 or 2
within the range of the selected
parameter or of the PV Span
for Deviation configurations
90
AxSxTY
A1S1
A1S2
A2S1
A2S2
1105
1106
1107
1108
Alarmx Setpointx
Type
X = 1 or 2
0
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
NONE No Alarm
IN 1 Input 1
IN 2 Input 2
PROC Process Variable
DE Deviation
OUT Output
SHED Shed Communications
E-ON Event ON(SP Prog)
E-OF Event OFF(SP Prog)
MAN Alarm on Manual
RSP Remote Setpoint
FSAF Failsafe
PrRT PV Rate of Change
DI Alarm on Digital Input
DE 11 DEV Alarm SP2 based
BRAK Loop break alarm
NONE
AxSxHL
A1S1
A1S2
A2S1
A2S2
1109
1110
1111
1112
Alarmx Setpoint
State
X = 1 or 2
0
1
LOW Low Alarm
HIGH High Alarm
HIGH
AxSxEV
A1S1
A1S2
A2S1
A2S2
1109
1110
1111
1112
Alarmx Segment
Event x
X = 1 or 2
0
1
BEGN Beginning of Segment
END End of Segment
BEGN
ALHYST
1113
Alarm Hysteresis 0.0 to 100.0 % of span or full
output as appropriate
0.0
ALARM1
1114
Latching Alarm
Output
0
1
NO L
LACH
NO L
BLOCK
1115
Alarm Blocking 0
1
2
3
DIS Disable Blocking
BK1 Block Alarm 1 only
BK2 Block Alarm 2 only
BK12 Blocks both Alarms
DIS