Loading...
Figure 5-16 Binding cables in dierent colors
Table 5-4 Cable bundle binding interval
Cable Bundle Diameter (mm) Binding Interval (mm)
< 10 150
10-30 200
> 30 300
Cable Bending
Table 5-5 Cable bending rules
No.
Cable Bending Rule
1 Cables are not overly bent as over bending may damage the
cable cores.
2 Unless otherwise stipulated, the bending radius should be 10
times greater than the cable diameter if the installation space is
sucient.
3 Cables are not tied where they bend, as shown in Figure 5-17.
4 Cables must be a little longer than the exact cable route length
to facilitate plug and unplug, as shown in Figure 5-18.
5 Cables should be neatly and loosely arranged to eliminate
abnormal stress on certain cables, as shown in Figure 5-19.