(1) Monitoring cable outlet
Step 7 (Optional) Connect the re linkage cables.
The customer can select a cable connection method based on the actual
requirement:
● Scenario 1: single-input or dual-input PDC; one pair of
re extinguishing input
cables control all loads to power o.
– Single-input PDC: Connect the positive and negative terminals of the re
control cable to the 24VDC(+) and 24VDC(-) wiring terminals at the rear
right of the cabinet respectively.
– Dual-input PDC: Connect the positive and negative terminals of the
re
control cable to the 24VDC(+) and 24VDC(-) wiring terminals at the rear
left or rear right of the cabinet respectively.
● Scenario 2: dual-input PDC; either of the two pairs of
re extinguishing input
cables can control all loads to power
o.
– Separate the two routes of re control cables and connect them to the
re extinguishing signal wiring terminals on both sides at the cabinet
rear. Connect the positive and negative terminals of each pair of control
cable to the 24VDC(+) and 24VDC(-) wiring terminals at the rear left and
rear right of the cabinet respectively.
1. 24 V DC cables routed into the PDC should be shielded cables.
2. Ensure that the polarities of 24 V DC cables routed into the PDC are correct.
Figure 5-47 Connecting the re linkage cables (scenario 1)
PDU8000 Modular Precision PDC V2.0
User Manual 5 Installation Guide
Issue 04 (2021-04-13) Copyright © Huawei Technologies Co., Ltd. 66