LUNA2000-200KWH-2H1 Smart String ESS
User Manual
Copyright © Huawei Technologies Co., Ltd.
3 System Power-On
3.1 Check Before Power-On
3.1.1 General Check
The equipment is intact and free from rust or paint flake-off.
If paint flakes off, repaint the equipment.
The labels on the device are clear. Damaged labels must be
replaced.
Cable sheathings are properly wrapped and not damaged.
Cable hoses are intact.
Cables are connected in the designed positions.
Terminals are prepared as required and securely connected.
Labels on both ends of each cable are clear and specific, and
attached in the same direction.
Electrical and ELV cables are routed separately.
Cables are neat and tidy.
Cable tie joints are evenly cut without burrs.
Cables are placed properly and with slack at bending points
to avoid stress.
Cables are routed neatly without twists or crossovers in the
cabinets.
The copper bar is not deformed, and the plastic dip coating is
not damaged.
The DC LV Panel switch is set to OFF.
The battery rack switch is set to OFF.