LUNA2000-200KWH-2H1 Smart String ESS
User Manual
4 SmartLogger Web-based Deployment
Copyright © Huawei Technologies Co., Ltd.
Protect the password by changing it periodically, and keep it secure. If you lose the password, the
device must be restored to its factory settings. Huawei will not be held liable for any losses resulting
from improper password management.
You will be locked out for 10 minutes after five failed password attempts in five minutes.
A dialog box with recent login information is displayed after login. Click OK.
----End
Follow-up Procedure
If any page is blank or a menu cannot be accessed after you log in to the WebUI, clear the
cache, refresh the page, or log in again.
4.2 Checking the SmartLogger Software Version
Choose Monitoring > Logger (Local) > About and check that the software version is
FusionSolar V800R021C10SPC110 or later.
4.3 Upgrading the SmartLogger
If the SmartLogger software version is not FusionSolar V800R021C10SPC110 or later, upgrade the
SmartLogger.
Obtain the SmartLogger upgrade package from the Company.
Step 1 Choose Maintenance > Software Upgrade, upload the SmartLogger upgrade package, select
the device, and upgrade the SmartLogger.
Step 2 After the software upgrade is complete, the SmartLogger automatically restarts. Log in to the
SmartLogger WebUI again 2 minutes later.
----End
4.4 Setting Battery Modules
Step 1 Choose Monitoring > ESR > Running Param. > Settings, and set Number of battery
modules to 12.
Step 2 Choose Monitoring > ESU > Running Param., select Delete invalid battery module, and
submit the settings.
Step 3 Choose Monitoring > ESU > Running Param., click in the upper right corner, and
wait for 2 minutes.
Step 4 Choose Monitoring > ESR, click +, and verify that the ESM-1 to ESM-12 status indicators
under the ESR are all green or yellow.
Step 5 Choose Monitoring > ESM > About and check the software versions of ESM-1 to ESM-12.