LUNA2000-200KWH-2H1 Smart String ESS
User Manual
Copyright © Huawei Technologies Co., Ltd.
3.1.2 ESS Installation Check
Enclosure
The installation meets the design
requirements.
The container is level, and each door
opens normally.
The container surface is free from cracks,
dents, and scratches. If the paint flakes off,
repaint the device.
Each container has at least two ground points
and is grounded securely with a ground
resistance of 0.1 ohm or less.
The number and positions of external
accessories installed meet design
requirements.
All labels are correct, clear, and complete.
Interior
The circuit breaker is in OFF.
The copper bars are not deformed, and no
foreign objects are placed on the copper bars.
The bolts for installing the cables are tightened
and the cables are not loose.
Cable holes have been sealed.
The battery pack surface is intact.
Foreign objects such as tools and remaining
materials are cleared.
Baffle plate for the
power distribution area
The baffle plates in the power distribution area
are free from cracks, dents, scratches, cracks,
and looseness.
The SPD indicator is green.
Subcomponent (CMU,
adapter, and
rack-mounted
integrated gas fire
extinguisher)
All components are intact.