4 SmartLogger Web-based Deployment
Copyright © Huawei Technologies Co., Ltd.
113
Parameter
Description
Adjustment
deadband
Allowed fluctuation of the target grid power for the
grid-connection point
Automatic SOC
calibration
EnabledAutomatic SOC calibration is enabled. If the total
charge and discharge energy reaches the threshold or the
calibration function has not been triggered for 30 days, the SOC
automatic calibration is performed. During calibration, the
cut-off SOC settings will be ineffective and the response of the
charge/discharge power may be impacted temporarily.
DisabledAutomatic SOC calibration is disabled.
Start time
Set the Charge/Discharge time. A maximum of 14 time segments
can be set. You can set a cycle by week by clicking the buttons
corresponding to Mon. through Sun. in the Repeat box. The
buttons are blue by default, indicating selected. After you click it,
the button turns gray.
To
Charge/Discharge
Repeated
6. Connect to a Huawei network management system (NMS.)
7. Connect to a third-party management system. Select IEC104.
8. Connect to third-party devices.
9. The settings are complete.
----End
4.6 System Setup
Prerequisites
Start up the system when needed.
Procedure
Step 1 Choose Maintenance > Connect Device on the SmartLogger WebUI.
Step 2 Click in the upper right corner to start devices in batches.