LUNA2000-200KWH-2H1 Smart String ESS
User Manual
Copyright © Huawei Technologies Co., Ltd.
reconnect the cable properly.
2. Check whether the power cable of the
device is loose. If yes, connect it securely.
3. If the fault persists, contact your technical
support.
SmartMo
dule
Commun
ication
Failure
Cause ID = 1
SmartModule
communication failed.
1. Check whether the communication cable is
correctly connected to the device. If not,
reconnect the cable properly.
2. Check whether the power cable of the
device is loose. If yes, connect it securely.
3. Check whether a certificate expiration alarm
is displayed in the alarm list. If yes, contact
your technical support.
4. If the fault persists, contact your technical
support.
CMU
Commun
ication
Failure
Cause ID = 1
CMU communication
failed.
1. Check whether the communication cable is
correctly connected to the device. If not,
reconnect the cable properly.
2. Check whether the power cable of the
device is loose. If yes, connect it securely.
3. If the fault persists, contact your technical
support.
Fire
Suppressi
on
Module
Pressure
Insufficie
nt
Cause ID = 1
The gas pressure of the
fire suppression module is
insufficient for more than
three days.
Check the fire suppression module and the
pressure gauge, and replace the fire suppression
module.
Cause ID = 1
The temperature and
humidity control mode is
set to manual.
After the commissioning is complete, set the
temperature and humidity control mode to
automatic.
Cause ID = 1
There are too many faulty
exhaust fans.
Cause ID = 2
There are too many faulty
TCUs.
Cause ID = 1
Repair the exhaust fan based on the fault alarm.
Cause ID = 2
1. Repair the TCU based on the fault alarm.
2. On the maintenance screen, check that the
TCU is correctly connected.
Combusti
ble Gas
Detection
Malfunct
ion
Cause ID = 1
There are too many faulty
combustible gas sensors.
1. Repair the combustible gas sensor based on
the fault alarm.
2. On the maintenance screen, check that the
combustible gas sensor is correctly
connected.