Why is the grid voltage abnormal on my Huawei Inverter?
- TtaylordanaNov 16, 2025
If the Huawei Inverter grid voltage alarm occurs accidentally, it's possible the power grid is experiencing a temporary issue. The SUN2000 should automatically return to normal operation once the grid fault is resolved. If the alarm persists, verify that the grid voltage is within the acceptable range. Also, check if the AC voltage is normal, in case of a power outage or disconnection of the AC line or circuit breaker. If the grid A, B, or C phase voltage is higher than the allowable range, check whether the grid-tie point voltage is too high and contact your local power operator. If the grid A, B, or C phase voltage is less than the allowable range, change the grid overvoltage and undervoltage protection points on the SUN2000 APP, data collector, or NMS after obtaining approval from the l...