No
.
Name Type Conductor Cross-
Sectional Area
Outer
Diameter
Sourc
e
2 (Optional)
Battery cable
Common
outdoor PV
cable in the
industry
4–6 mm
2
5.5–9 mm Prepar
ed by
the
custo
mer
3 (Optional)
Battery signal
cable
Cat 5E
outdoor
shielded
network
cable
0.12–0.2 mm
2
4–11 mm Purcha
sed
from
Huaw
ei (5
m)
4 (Optional)
RS485
communicatio
ns cable
Two-core
outdoor
shielded
twisted pair
cable
0.2–1 mm
2
4–11 mm Prepar
ed by
the
custo
mer
5 (Optional)
Signal cable to
the rapid
shutdown
switch
Two-core
outdoor
shielded
twisted pair
cable
0.2–1 mm
2
4–11 mm Prepar
ed by
the
custo
mer
6 (Optional)
Grid
scheduling
signal cable
Five-core
outdoor
cable
0.2–1 mm
2
4–11 mm Prepar
ed by
the
custo
mer
7 AC output
power cable
Outdoor
copper
cable
4–6 mm
2
10–21
mm
Prepar
ed by
the
custo
mer
8 PE cable Single-core
outdoor
copper
cable
4–6 mm
2
10–21
mm
Prepar
ed by
the
custo
mer
● The minimum cable diameter must meet local standards.
● The factors that aect cable selection include the rated current, cable type, routing
mode, ambient temperature, and maximum expected line loss.
SUN2000-(5K-12K)-MAP0 Series
User Manual 5 Electrical Connections
Issue 01 (2024-05-13) Copyright © Huawei Digital Power Technologies Co., Ltd. 43