4.5 Setting ECO Mode
Prerequisites
The system is working in inverter mode.
Context
The UPS is set to non-ECO mode by default. Set the UPS to ECO mode when
energy saving is required.
In ECO mode, the bypass takes priority over the inverter in supplying power. If
the bypass fails, the UPS transfers to inverter mode.
Both a single UPS and the parallel system support the ECO mode for higher
eciency.
To avoid frequent transfer between ECO mode and normal mode, do not set
the ECO mode when the bypass input is unstable or is sensitive to load
changes.
ECO mode is not recommended when the load is less than 10%.
Before setting ECO mode, ensure that the bypass is working properly.
Procedure
Step 1 On the LCD, choose System Info > Settings > System Settings and set Working
mode to ECO. The information indicating that the UPS works in ECO mode is
displayed on the LCD.
Step 2 Set the ECO voltage range.
Figure 4-6 ECO parameters
Step 3 (Optional) If you set ECO mode in bypass mode, manually start the UPS inverter.
UPS5000-E-(30 kVA–120 kVA)-FM
User Manual 4 Operations