Parameter Setting
Port 443
Username admin
Password Changeme
c. Tap Power-on password activation and tap OK on the displayed screen
to complete the startup.
d. Complete and submit the startup report.
●
Oine activation
a. Tap
Oine Activation to access the Oine Activation screen.
b. Enter the information obtained from the UPS LCD screen on the Oine
Activation screen and tap Generate PWD.
c. Enter the generated startup password in the Password text box on the
UPS LCD, and press Enter to start the UPS.
d. Complete and submit the startup report.
----End
4.1.2.2 Settings Wizard
Procedure
Step 1 Set the language, time and date, network parameters, system parameters, and
battery parameters on the Settings Wizard screen.
Set system parameters with caution because the settings determine whether the
UPS can operate normally.
● Set Single/Parallel after double check. Incorrect setting may
aect the normal
UPS operation.
● Output voltage level refers to the line voltage level. Set it based on site
requirements.
● Set Output frequency correctly; otherwise, loads may be
aected and the UPS
may not work properly.
● Battery parameter settings are critical to battery maintenance, battery lifespan,
and UPS discharge time.
UPS5000-E-(30 kVA–120 kVA)-FM
User Manual 4 Operations
Issue 03 (2022-01-30) Copyright © Huawei Technologies Co., Ltd. 90