Item Specications
Voltage dip and temporary
interruption
IEC 61000-4-11
7.5 Mains Input Electrical Specications
Item Specications
Input system Three-phase four-wire + PE
Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)
Input voltage range 80–280 V AC (phase voltage)
At 30–40°C: The UPS works at full load when
the voltage is 187–280 V AC and is derated
to 40% load when the voltage is 187–80 V
AC.
At 0–30°C: The UPS works at full load when
the voltage is 176–280 V AC and is derated
to 40% load when the voltage is 176–80 V
AC.
Rated frequency 50 Hz/60 Hz
Input frequency range 40–70 Hz
Input power factor > 0.99 (full load)
> 0.98 (half load)
THDi ≤ 3% (linear load)
≤ 5% (non-linear load)
7.6 Bypass Input Electrical Specications
Item
Specications
Rated input voltage 380 V AC/400 V AC/415 V AC (line voltage)
Input voltage range Upper threshold: +10%, +15% (default), +20%,
+25% (when the voltage system is 380 V AC)
Upper threshold: +10%, +15% (default), +20%
(when the voltage system is 400 V AC)
Upper threshold: +10% (default), +15% (when the
voltage system is 415 V AC)
Lower threshold: –10%, –15%, –20% (default), –
30%, –40%, –50%, –60%
UPS5000-E-(30 kVA–120 kVA)-FM
User Manual 7 Technical Specications
Issue 03 (2022-01-30) Copyright © Huawei Technologies Co., Ltd. 122