Silk Screen Description Status Initial Status
SWITCH
STATUS_BP
Port for monitoring
the bypass input
circuit breaker
Connected: circuit
breaker ON
Disconnected:
circuit breaker OFF
Connected
SWITCH
STATUS_0V
Port for signal
ground
SPD Port for monitoring
the input AC surge
protective device
(SPD)
Connected: The
input AC SPD is
normal.
Disconnected: The
input AC SPD fails.
Connected
0V Port for signal
ground
NO TE
The dry contact interface card takes eect only after it is set on the monitoring system.
Set the unused dry contact signal to the unused status.
Set the EPO port to NO or NC as required.
When multiple UPSs are paralleled, all dry contact signals to be used need to connect to
each UPS.
Single cables require dual-insulated twisted cables. If the length of a power cable is
within 25–50 m, its cross-sectional area must be 0.5 mm
2
to 1.5 mm
2
.
Functions
The dry contact card allows the UPS to detect and manage the switch status of
the battery system (including the external battery switch) and implement remote
EPO.
Specications
Hot-swappable
0.5 U high
UPS5000-E-(30 kVA–120 kVA)-FM
User Manual 2 Overview