10 Technical Specications
Table 10-1 Physical specications
Item Specications
Cabling mode Routed in and out from the top
IP rating IP20
Communication Supports dry contacts, RS485 ports, and FE ports.
Supports SNMP and Modbus.
Dimensions (H x W x
D)
2000 mm x 800 mm x 1000 mm
Weight < 800 kg
Table 10-2 Environmental
specications
Item
Specications
Operating
temperature
0°C to 55°C
Temperature derating coecient: not derated at 0°C–
40°C, derated to 0.9 at 41°C–45°C, derated to 0.8 at
46°C–50°C, and derated to 0.7 at 51°C–55°C
Storage temperature –40°C to +70°C
Humidity 0%–95% RH (non-condensing)
Altitude 0–1000 m
When the altitude is greater than 1000 m, the power is
derated as described in IEC 62040-3. The upper limit of
the altitude is 4000 m.
UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module) 10 Technical Specications
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 98

Table of Contents