6 Installation
6.1 Installation Preparations
6.1.1 Site
6.1.1.1 Installation Environment
Before installing the UPS, note the following:
● Do not install the UPS in a high-temperature, low-temperature, or damp place
that is beyond the technical
specications.
● Install the UPS far away from water sources, heat sources, and inammable
and explosive materials. Keep the UPS free from direct sunlight, dust, volatile
gases, corrosive materials, and salty air.
● Do not install the UPS in environments with conductive metal scraps in the
air.
● The optimal operating temperatures for valve-regulated lead-acid (VRLA)
batteries are 20–30°C. Operating temperatures higher than 30°C shorten the
battery lifespan, and operating temperatures lower than 20°C reduce the
battery backup time.
● Ensure that the
oor or installation support can bear the weight of the UPS,
batteries, and battery racks.
UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module) 6 Installation