Figure 2-4 Conceptual diagram
2.5 Working Modes
2.5.1 Normal Mode
In normal mode, the rectier converts AC power into DC power. Then the inverter
converts DC power into AC output. At the same time, the rectier charges
batteries over a charger. The two conversions ensure high-precision and high-
quality output voltages, protecting loads from interferences such as input
harmonics, glitches, and voltage transients.
Figure 2-5 UPS conceptual diagram in normal mode
2.5.2 Bypass Mode
When the UPS detects that the power module experiences overtemperature,
overload, or other faults that may shut down the inverter, the UPS automatically
transfers to bypass mode. At the same time, the
rectier is started and charges
batteries over a charger. In bypass mode, loads are powered by the bypass
UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module) 2 Product Overview