6.1.1.2 Installation Clearances
Figure 6-1 UPS dimensions
Reserve the following clearances around the cabinet to facilitate operations and
ventilation:
● Reserve a clearance of at least 950 mm from the front of the cabinet for
ventilation and operations.
● Reserve a clearance of at least 500 mm from the top of the cabinet for
operations.
● Reserve a clearance of at least 500 mm from the rear of the cabinet for
ventilation.
● Reserve a clearance of at least 800 mm if you need to perform operations at
the rear of the cabinet.
6.1.2 Tools and Instruments
● Use insulated tools to avoid electric shocks.
● The following table lists only the common tools for installation and cable
connection. For more dedicated tools required, see the document for each
component. Prepare tools based on site requirements.