Table 4-4 Specications
Item Specications
Dimensions (H x W x D) 200 mm x 600 mm x 600 mm
Weight < 50 kg
4.3 Control Module
4.3.1 Overview
The control module in a standard conguration contains two ECMs, one dry
contact card, and one monitoring interface card from left to right. The four cards
are hot-swappable. One subrack is reserved above the dry contact card. A
backfeed protection card or dry contact extended card can be inserted into the
subrack.
Figure 4-3 Signal panel of the control module
(1) Ground terminal
(2) Parallel port 1 (3) BSC port 1 (4) Ready switch on
ECM 1
(5) ECM 1 indicators (6) Parallel port 2 (7) BSC port 2 (8) Ready switch on
ECM 2
(9) ECM 2 indicators (10) Dry contact card (11) Dry contacts (12) Monitoring
display unit (MDU)
port
(13) RS485 port (14) FE port (15) COM2 port (16) COM1 port
(17) Battery
temperature sensor
port
(18) Optional card
subrack cover
Ports are protected by a security mechanism.
4.3.2 ECM
● As a control interface for the entire system, the ECM communicates with each
module and provides a bus for communication between the dry contact card
and the system control card. The ECM ensures equalized output currents
between modules so that load power is equally shared.
UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module) 4 Component Description
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 29