Item Expected Result Troubleshooting
Battery
operating
temperature
1. The ambient battery
temperature is 25±5°C.
2. The battery operating
temperature is lower than
battery temperature +20°C.
3. Battery charge and
discharge conditions meet
the requirements
specied
in the battery
specications.
1. Identify the cause of an
abnormal battery operating
temperature.
2. If the fault persists, contact
Huawei technical support.
Charge
voltage of
battery string
Equalized charging voltage:
(2.35 V/cell ±1%) x Single
battery voltage/2 x Number
of batteries in a battery
string
Float charging voltage:
(2.25 V/cell ±1%) x Single
battery voltage/2 x Number
of batteries in a battery
string
1. If the voltage drop between
the battery string output
terminals and the battery
input terminals at the UPS
side is greater than 1% of
the battery string voltage,
check whether the cable
between the battery string
and the UPS is excessively
long, or the cable diameter
is excessively small.
2. Check whether the
equalized charging voltage
and
oat charging voltage
are correctly set for the
UPS.
3. If the fault persists, contact
Huawei technical support.
8.2.3 Quarterly Maintenance
Table 8-5 Quarterly maintenance
Item
Expected Result Troubleshooting
Battery temperature
sensor measurement
accuracy
The dierence between
the temperature
measured by the
temperature sensor and
the temperature displayed
on the MDU is less than
3°C.
1. Install the temperature
sensor in the correct
position.
2. Replace the battery
temperature sensor.
UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module) 8 Routine Maintenance
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 92