Figure 7-4 BCB connection settings
----End
7.2 Shutting Down and Powering
O the UPS
Context
If the bypass is normal, the UPS transfers to bypass mode after the inverter is shut
down; if the bypass is abnormal, the UPS supplies no power after the inverter is
shut down. Before shutting down the UPS, ensure that all loads have been shut
down.
Procedure
Step 1 Shut down the inverter.
● Shutting down the inverter on the LCD
Choose Common Functions > Inv. OFF. After
conrmation, the inverter is
shut down.
You can also choose System Info > Maintenance > Inv. OFF to shut down the
inverter.
● Shutting down the inverter on the WebUI
Choose Monitoring > UPS System > Running Control, and click Inv. OFF.
If the inverter shuts down and the bypass is normal, the UPS transfers to bypass
mode. The Bypass mode alarm is displayed on the LCD.
UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module) 7 System Commissioning
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 73