Indicator Color Status Description
Blinking
at short
intervals
The module is not congured, the inverter
software and rectier software are being
upgraded, or the inverter software is being
upgraded (blinking at 4 Hz, on for 0.125s and
o for 0.125s).
O The software is being upgraded.
Alarm
indicator
Yellow Steady
on
A minor alarm is generated for the inverter or
rectier.
O There is no minor alarm for the inverter or
rectier, or the software is being upgraded.
Fault
indicator
Red Steady
on
A critical alarm is generated for the inverter or
rectier.
O There is no critical alarm for the inverter or
rectier, or the software is being upgraded.
Table 4-2
Specications
Item
Specications
Rated output capacity 100kVA/100kW
Dimensions (H x W x
D)
130 mm x 442 mm x 750 mm
Weight < 55 kg
4.2 Bypass Module
The UPS works in bypass mode under the following circumstances:
● The ECO mode is used and the bypass voltage is within the specied range.
● The power module overload times out.
● Both active and standby energy control modules (ECMs) in the system are
abnormal.
● The system runs abnormally.
● The UPS is transferred to bypass mode manually.
UPS5000-H-(400 kVA-600 kVA)
User Manual (100 kVA Power Module) 4 Component Description
Issue 01 (2020-11-30) Copyright © Huawei Technologies Co., Ltd. 27